Ventilation Efficiencies of Task/Ambient Conditioning Systems with Desk-Mounted Air Supplies

Publication Type

Conference Paper

Date Published

08/1999

Authors

Faulkner, David, William J. Fisk, Douglas P. Sullivan, David P. Wyon

Abstract

In laboratory experiments, we investigated the ability of two task/ambient conditioning systems with air supplied from desk-mounted air outlets to efficiently ventilate the breathing zone of heated manikins seated at desks. In most experiments, the task conditioning systems provided 100% outside air while a conventional ventilation system provided additional space cooling but no outside air. Air change effectiveness (i.e., exhaust air age divided by age of air at the manikin's face) was measured. Tracer gases simulated the release of pollutants from nearby occupants and from the floor covering, and the associated pollutant removal efficiencies (i.e., exhaust air concentrations divided by concentrations at manikin's face) were also measured. High values of air change effectiveness (~ 1.3 to 1.9) and high values of pollutant removal efficiency (~ 1.2 to 1.6) were measured when these task conditioning systems supplied 100% outdoor air at a flow rate of 7 to 10 L s-1 per occupant.

Journal

Indoor Air '99 Conference, August 8-13, 1999

Year of Publication

1999

Organization

Residential Building Systems, Whole Building Systems Department, Building Technology and Urban Systems Division, Indoor Environment Group, Sustainable Energy Department, Energy Analysis and Environmental Impacts Division

Research Areas

IEG Commercial Buildings, EAEI Healthy & Efficient Buildings

Related Files

PDF (36.28 KB) (link is external)

        

©2025 Energy Technologies Area, Berkeley Lab
Lawrence Berkeley National Laboratory (link is external)
  • twitter(link is external)
  • instagram(link is external)
  • LinkedIn(link is external)
  • facebook(link is external)
  • youtube(link is external)
  • DOE logo
  • UC logo
A U.S. Department of Energy National Laboratory Managed by the University of California
Questions & Comments(link is external) Privacy & Security Notice(link is external)